Gai-tronics 12579-003 Monitored Relay Module (MRM) Instrukcja Użytkownika Strona 9

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 17
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 8
Pub. 42004-716L2C
Model 12579-003 Monitored Relay Module Page
9 of 16
f:\standard ioms - current release\42004 instr. manuals\42004-716l2c.doc
05/12
Mode 3: IDC Single Normally-Closed (N.C.) Switch
In this configuration, only one normally-closed dry contact closure may be installed per supervised line.
In this mode, the loop is monitored for open circuits, wire-to-wire short circuits (across + and -), and
ground faults. When the contact closure is not active (closed), the 15 k is bypassed and the circuit sees
only the 5.1 k load.
Figure 7. IDC Single Normally-Closed Switch
This change is sensed by the MRM and indicates to the MRM that the contact closure is active. If there is
a short across L1 and L2, if either leg is grounded, or if a break occurs on either leg, the MRM indicates
that a fault has occurred.
N
OTE: The terminating resistors are not included with the MRM. These resistors are included in a kit
(12509-004), which must be ordered separately.
Przeglądanie stron 8
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

Komentarze do niniejszej Instrukcji

Brak uwag